American journal of epidemiology
-
In the period August 10-29, 1986, 29 confirmed cases of Legionnaires' disease occurred in Sheboygan, Wisconsin; two cases were fatal. No common source of indoor exposure was identified. Water specimens were obtained from all known cooling tower units in Sheboygan; Legionella pneumophila serogroup 1 was isolated at 1 x 10(6) colony-forming units per liter from a specimen obtained August 27 at plant A. ⋯ Of 29 persons with Legionnaires' disease, 21 lived or worked within one mile (1.6 km) of plant A; seven of the remaining eight visited within one to two miles (1.6 to 3.2 km) of plant A from three to seven days before onset of illness. Attack rates were highest for persons living within 0.5 mile (0.8 km) of plant A. These findings associate a cooling tower with community-acquired Legionnaires' disease and suggest that dissemination of Legionella may occur over longer than previously recognized distances.